The Module Configuration screen provides information about the output module setup. Click Edit to make changes to the settings. The fields are described in the table below.
Field / Section |
Description |
Alarm Elevation |
Number of seconds the alarm must persist before elevating to the next higher alarm level (or set to DISABLE) |
Module Status |
Shows module as being either ENABLED or DISABLED |
Module Parameters |
To set module parameters described below |
Clk C Bypass |
Enables or Disables bypass mode to support Clock C |
Zero Suppression |
Select ON (eliminates leading zeros) or select OFF |
Mode |
Sets E1 framing mode to either CCS or CAS |
CRC |
Cyclic Redundancy Check - Select ON (verifies transmission) or OFF |
SSM |
Synchronization Status Messages - Select ON (provides clock quality information to any equipment that uses synchronization inputs) or OFF |
SSM Bit |
Sets the E1 bit position to 4,5,6,7, or 8 (SSM Bit is only shown for E1 outputs) |